Sipaulovi Village                                 
Wastewater Treatment Calculations                              
Oswald System                                
DCS Solutions                                
                                 
Domestic wastewater flow:              
0.09 mgd 340650 liters/day           = value is calculated by spreadsheet      
                  = value must be entered        
Commercial wastewater flow:                              
0.007 mgd 26495 liters/day                          
                                 
Combined wastewater flow:                              
0.097 mgd 367145 liters/day                          
                                 
BOD loading (domestic):                                
250 mg/L 187.7833 pounds/day                          
                                 
BOD loading (commercial):                              
400 mg/L 23.36859 pounds/day                          
                                 
BOD combined:                                
260.8247423 mg/L                              
                                 
Percolation:                                
0 "/yr                              
                                 
Evaporation:                                
78.9 "/yr                              
                                 
Hydraulic Retention Time:                              
20 days                              
                                 
Advanced Facultative Pond Calculations:                            
                                 
Number of cells:                                
2                                
                                 
Flow per cell:                                
0.0485 mgd                              
0.049 nearest whole number                          
                                 
Volume of AFP:                                
  0.98 million gallons 131320 ft3                        
                                 
Depth:                                  
10 ft         `                    
                                 
Surface Area:                                
  13132 ft2 per cell 0.30146924 acres per cell                      
                                 
To allow for any one cell to be taken out of service:                          
S.A.= 25996 ft2 per cell, with one offline 0.596786 acres per cell                    
                                 
      Use: 0.6 acres per cell                    
                                 
Total acres:                                
1.2 acres                               
                                 
Hydraulic Detention Time Check:                              
40.30871753 days (greater than necessary, so dimensions are acceptable)                    
                                 
BOD loading:                                
217.3539519 lbs/acre/day  (average)                          
434.7079038 lbs/acre/day (max w/one cell offline)                        
                                 
Fermentation Pit:                                
                                 
Temperature at bottom:                                
4 deg. C (Oswald Table VIII-1, pg 8-12)                        
                                 
Flow:                                  
0.097 mgd                              
                                 
Max permissible loading:   (Assume 2% solids)                          
  0.008 lb/ft3/day                              
                                 
Settleable solids:                                
  32603.09278 ft3                              
                                 
BOD per person per day:                                
0.2 lbs BOD/person/day (Metcalf & Eddy, Table 3-12, pg. 182)                    
                                 
Equivalent people (incorporates commercial & domestic BOD into a per person loading):                    
1304.123711 people                              
                                 
Design life:                                
20 years                              
                                 
Inert Ash per person per year:                              
  0.1 ft3/person/year (Oswald, p 8-24)                        
                                 
Total Inert Ash:                                
  2608.247423 ft3                              
                                 
Grit per mgd:                                
  5 ft3/mgd   (Oswald, p 8-24)                        
                                 
total grit:                                  
  3540.5 ft3                              
                                 
Total volume needed for settleables:                              
  38751.84021 ft3                              
                                 
Side Slopes:                                
3 :1                              
                                 
Max Surface Area (to avoid overturning) 10764 ft2                          
  10764 ft2     (Oswald, p 9)                      
                                 
Min area at bottom (to allow equipment access): 144 ft2                          
  144 ft2     (Oswald, p 9)                      
                                 
Min Depth (to allow for gas/sludge separation): 13.3 ft                          
13.5 ft     (Oswald, p 9)                      
                                 
Surface Dimensions:                                
93 ft         by 93 ft                          
                                 
Rounding up:                                
93 ft         by 93 ft                          
                                 
Total surface area:                                
  8649 ft2 (this value is less than maximum allowable to avoid overturning)                  
                                 
Area at the middle (used to determine volume):                            
  2756.25 ft2                              
                                 
Volume of "minimum" pit:                              
  44590.5 ft3                              
                                 
Number of pits required for settleable solids:                            
0.869060455 pits   rounded up: 1 pits                      
                                 
Number of pits needed to be able to take one offline:                          
2 pits (make sure number of cells equals number of pits)                    
                                 
Total pit volume (with additional pit):                              
  89181 ft3   rounded up: 90000 ft3                      
                                 
Hydraulic retention time check:                              
6.940206186 days   (>2 days, Oswald p 8-21)                      
                                 

BACK                    TOP